Gas Leaks monitoring system

- Main Features
- Applications

- Complete kit with **1 central unit**, **emergency pushbutton**, **alarm bell** and up to 4 **MLD gas detectors**
- Visual and audible alarm control unit
- Rechargeable backup battery
- Illuminated pushbutton for manual alarm

- Test chambers for HVAC units using flammable refrigerants
- Production lines and gas charging stations for HVAC units
- Laboratories for testing with flammable gases and technical rooms
- Complex HVAC-R units requiring multiple gas leak detection points
- Engine rooms in marine applications

Services

---

###### Professional and fast quote

---

###### Product usually available on stock

---

#

- ASK for "Just in time" delivery

### More questions?

[+39 02 3340 0846](https://gvzcomp.it/tel:390233400846) or [Contact us](https://gvzcomp.it/contact)

### Questions?

[+39 02 3340 0846](https://gvzcomp.it/tel:390233400846)
or [Contact us](https://gvzcomp.it/contact)

### Description

## ![](https://gvzcomp.it/images/sample/PEGO-GCK-preview-2.jpg)



## Complete solution for gas leak monitoring: Gas Control Kit



The Gas Leak Monitoring Kit consists of one or more (up to 4) **MLD (Molecular Leakage Detector) gas detectors** and a **control unit** equipped with audible and visual alarms, backup battery, illuminated emergency pushbutton for manual alarm activation, and a secondary visual/acoustic siren for remote signaling.
The kit enables **pre-alarm and gas leak alarm signaling** for a wide range of gases (A2L and A3 refrigerants, methane, propane, hydrogen, etc.).
The system is designed to operate even in the event of a temporary power outage, thanks to the **backup battery integrated into the main control unit**.
In addition to visual and audible alarms, the control unit provides **two dry-contact relays** and a **dedicated Modbus communication line** for integration with third-party systems.



---



- **Visual and audible alarm control unit**, compliant with **UNI EN 378-1**, featuring an integrated siren and flashing light for gas leak alarm signaling, as well as a backup battery for blackout conditions. The unit includes **dual relays** providing dry contacts (closed when alarm is active) that can be used to activate remote alarm signaling. It also features **dual RS-485 serial lines with Modbus RTU protocol**: one dedicated to gas detector management and one available for integration with third-party systems.
- **Bluetooth programming** via dedicated mobile app
- **Rechargeable backup battery** with battery status and efficiency monitoring
- Alarm control unit equipped with a **mute button** to silence gas alarms during periodic functional testing
- **MLD gas leak detectors** to be installed at the required locations, with separate pre-alarm and alarm signaling. Up to **4 gas sensors** can be connected in series via Modbus
- **Emergency pushbutton station** to be installed in a location easily accessible to the operator. It features an **illuminated pushbutton for manual alarm**. LED illumination is permanent to ensure visibility even in dark conditions. Up to **4 pushbuttons** can be connected
- **Secondary visual and audible alarm** for gas leak signaling, to be installed in a location separate from the control unit (optional)
- GAS TARGET - **Refrigerants**: R290 – R50 – R170 – R600 – R600a – R601 -R1270 – R32 – R454A - R454B - R454C – R1234ze -**Flammables**: butane, ethane, hydrogen, isobutane, isobutylene, isopropanol, methane, methyl ethyl ketone, octane, pentane, propane, propylene, toluene, xylene



| Control Unit Parameter | Specification |
| --- | --- |
| Dimensions | 203 × 193 × 79 mm |
| Weight | 3 kg |
| Power supply | 230 VAC, 50/60 Hz |
| Max. power consumption (main supply) | 10 VA |
| Backup battery | 12 VDC Ni-MH, 1300 mAh |
| Full recharge time | 10 h |
| Operating autonomy | 10 h (with fully charged battery) |
| Operating temperature | -5 ÷ +45 °C |
| Acoustic characteristics | Type: piezoelectric – Sound level: 90 dB @ 1 m |
| Visual indication | Flashing red LED, 12 VDC |
| Alarm / AUX relays | No. 2 – 5 A AC1 (SPDT) |
| Supervision | TeleNet / Modbus RTU |
| Serial communication | Modbus RTU |
| Bluetooth | BLE with myPego app |
| Protection rating | IP65 |

- Filter by Refrigerant - R50 (Methane) - R170 (Ethane) - R290 (Propane) - R600 (Butane) - R600a (Isobutane) - R601(Pentane) - R1270 (Propylene) - R1150 (Ethylene)
- Applications [HVAC](https://gvzcomp.it/applications/hvac)[Industrial](https://gvzcomp.it/applications/industrial)[Marine](https://gvzcomp.it/applications/marine)
- Brands GVZ Custom Solutions
- Technology MPS™
- Type Monitoring System

### Documentation

[### Datasheet

PDF | 300.42 KB](https://gvzcomp.it/component/djcatalog2/?format=raw&task=download&fid=3815#.pdf)

### Related products